Enhancement of a reduced order doubly fed induction generator model for wind farm transient stability analyses

dc.contributor.authorDöşoğlu, Mehmet Kenan
dc.contributor.authorArsoy, Ayşen Basa
dc.date.accessioned2020-05-01T12:11:53Z
dc.date.available2020-05-01T12:11:53Z
dc.date.issued2016
dc.departmentDÜ, Teknoloji Fakültesi, Elektrik-Elektronik Mühendisliği Bölümüen_US
dc.descriptionMehta, Bhinalkumar Bakulbhai/0000-0002-4638-2791; Mehta, Bhinalkumar Bakulbhai/0000-0002-4638-2791en_US
dc.descriptionWOS: 000374325800009en_US
dc.description.abstractDynamic modeling of a doubly fed induction generator (DFIG) implemented for wind power systems is very important for transient stability. The rotor dynamic model (RDM) as well as the reduced order model (ROM) of a DFIG has been developed for transient analysis purpose. The performances of reduced order DFIG models with/without RDM have been compared. Modeling and analyses have been carried out in MATLAB/SIMULINK. Comparison of system behaviors against 3 phase fault is made between without RDM and with RDM. Several parameters such as output voltage, active power, speed, electrical torque variations, and d-q axis stator and rotor current variations of the DFIG along with a 34.5 kV bus voltage have been examined. In addition, the responses of DFIG output voltage and electrical torque have been compared for the cases of full order and reduced order DFIG models with rotor dynamics. It has been seen that the system becomes stable in a short time when the rotor dynamic is included in a reduced order DFIG model.en_US
dc.identifier.doi10.3906/elk-1402-195en_US
dc.identifier.endpage2134en_US
dc.identifier.issn1300-0632
dc.identifier.issn1303-6203
dc.identifier.issue4en_US
dc.identifier.scopusqualityQ3en_US
dc.identifier.startpage2124en_US
dc.identifier.urihttps://doi.org/10.3906/elk-1402-195
dc.identifier.urihttps://hdl.handle.net/20.500.12684/6238
dc.identifier.volume24en_US
dc.identifier.wosWOS:000374325800009en_US
dc.identifier.wosqualityQ4en_US
dc.indekslendigikaynakWeb of Scienceen_US
dc.indekslendigikaynakScopusen_US
dc.indekslendigikaynakTR-Dizinen_US
dc.language.isoenen_US
dc.publisherTubitak Scientific & Technical Research Council Turkeyen_US
dc.relation.ispartofTurkish Journal Of Electrical Engineering And Computer Sciencesen_US
dc.relation.publicationcategoryMakale - Uluslararası Hakemli Dergi - Kurum Öğretim Elemanıen_US
dc.rightsinfo:eu-repo/semantics/openAccessen_US
dc.subjectDoubly fed induction generator (DFIG)en_US
dc.subjectreduced order model (ROM)en_US
dc.subjectrotor dynamic modeling (RDM)en_US
dc.subjecttransient stabilityen_US
dc.titleEnhancement of a reduced order doubly fed induction generator model for wind farm transient stability analysesen_US
dc.typeArticleen_US

Dosyalar

Orijinal paket
Listeleniyor 1 - 1 / 1
Yükleniyor...
Küçük Resim
İsim:
6238.pdf
Boyut:
208.87 KB
Biçim:
Adobe Portable Document Format
Açıklama:
Tam Metin / Full Text