An Assessment on Aging Model of IEEE/IEC Standards for Natural and Mineral Oil-Immersed Transformer
dc.contributor.author | Biçen, Yunus | |
dc.contributor.author | Çilliyüz, Yusuf | |
dc.contributor.author | Aras, Faruk | |
dc.contributor.author | Ayduğan, Güzide | |
dc.date.accessioned | 2020-04-30T22:39:09Z | |
dc.date.available | 2020-04-30T22:39:09Z | |
dc.date.issued | 2011 | |
dc.department | DÜ, Düzce Meslek Yüksekokulu, Elektronik ve Otomasyon Bölümü | en_US |
dc.description | IEEE International Conference on Dielectric Liquids (ICDL) -- JUN 26-30, 2011 -- Trondheim, NORWAY | en_US |
dc.description | Faruk ARAS, Dr./0000-0001-5513-9139 | en_US |
dc.description | WOS: 000295317700042 | en_US |
dc.description.abstract | This paper presents an assessment on aging model of IEEE and IEC standards using thermal model of oil-immersed power transformer for natural ester and mineral oil. For this purpose, a model created for the analysis of behavior transient thermal performance with aging both of natural ester and mineral oils. Thermal model of the transformer is based on thermal-electrical analogy that is calculated separately for natural and mineral oils covering top-oil and hot-spot temperatures. The hot-spot temperature values of each ester/oil are used to calculate aging parameters which include the aging acceleration factor, time dependent relative aging rate and insulation life loss variations. | en_US |
dc.description.sponsorship | IEEE, SINTEF Energy Res, NTNU - Norwegian Univ Sci & Technol | en_US |
dc.description.sponsorship | Unit of Kocaeli UniversityKocaeli University [2010/33, 2010/37] | en_US |
dc.description.sponsorship | This work is supported by the Scientific Research Projects Unit of Kocaeli University. Project numbers: 2010/33 and 2010/37. | en_US |
dc.identifier.isbn | 978-1-4244-7355-7 | |
dc.identifier.uri | https://hdl.handle.net/20.500.12684/2618 | |
dc.identifier.wosquality | N/A | en_US |
dc.indekslendigikaynak | Web of Science | en_US |
dc.indekslendigikaynak | Scopus | en_US |
dc.language.iso | en | en_US |
dc.publisher | Ieee | en_US |
dc.relation.ispartof | 2011 Ieee International Conference On Dielectric Liquids (Icdl) | en_US |
dc.relation.publicationcategory | Konferans Öğesi - Uluslararası - Kurum Öğretim Elemanı | en_US |
dc.rights | info:eu-repo/semantics/closedAccess | en_US |
dc.subject | aging | en_US |
dc.subject | insulation | en_US |
dc.subject | thermal model | en_US |
dc.subject | natural oil | en_US |
dc.subject | trasformer | en_US |
dc.subject | temperature | en_US |
dc.subject | loadability | en_US |
dc.title | An Assessment on Aging Model of IEEE/IEC Standards for Natural and Mineral Oil-Immersed Transformer | en_US |
dc.type | Conference Object | en_US |
Dosyalar
Orijinal paket
1 - 1 / 1
Küçük Resim Yok
- İsim:
- 2618.pdf
- Boyut:
- 707.58 KB
- Biçim:
- Adobe Portable Document Format
- Açıklama:
- Tam Metin / Full Text