Döşoğlu, Mehmet KenanArsoy, Ayşen Basa2020-04-302020-04-3020119786050102048https://hdl.handle.net/20.500.12684/3937th International Conference on Electrical and Electronics Engineering, ELECO 2011 -- 1 December 2011 through 4 December 2011 -- Bursa -- 88625In this study, the systems connect wind farm various voltage sag wind Farm DC link voltage, system buses voltage examined. For study of various transient stability 7.2 MVAr Static Var Compensator (SVC) is used. In the wind farm examined, 6 MW Double Feed Induction Generator (DFIG) is used. Also it examined 3 phase fault, induction motor, both 3 phase fault and induction motor together in wind farm. The results achieved have proved that SVC yield good results when used in terms of transient stability of the system., SVC was found to be effective and successful for eliminating instability in a very short period of time. © 2011 Chamber of Turkish Electric.eninfo:eu-repo/semantics/closedAccessInvestigation of various voltage sag analyses in wind farm through SVCConference ObjectI13I17